SWIMMING POOL AT LAHOREGiven Data:Swimming Pool Water Surface Area=980 Sqft(91M2)Water Temperature=290CRoom Temperature=290CRoom Humidity=50%(A)Evaporation from Water Surfaces.M= α .A.(x1-x2)CpWhereM=Moisture Load, kg/hrα =Coefficient of heat transfer, =1.5W/m2.KCp=The airs specific thermal capacity=1000J/kg.KA=Water surfacem area=91m2x1=Moisture content of saturated air =0.025kg / kg(as per attached chart)at 290C & 100% Humidity x2=Moisture content of room air=0.0125kg / kg(as per attached chart)at 290C & 50% Humidity M=1.5x91x(0.025-0.0125)x***006.1425kg/hr(B)Unintentional VentilationM=qv . Q .(x1-x2)WhereM=Moisture Load, kg/hrqv=Infiltration=0.23m3/sQ=Air density=1.2kg / m3x1=Moisture content of outdoor air=0.007kg / kg(as per attached chart)at 450C & 81 W.Bx2=Moisture content in room air=0.017kg / kg(as per attached chart)at 290C & 50% Humidity M=0.23x1.2(0.007-0.017)x3600=9.936kg/hr(C)Occupancy load=15Person.Average Evaporation=40g per person=15x40/10000.6kg/hrTotal Moisture Load kg/hrA=6.143kg/hrB=9.936kg/hrC=0.6kg/hr16.679kg/hrSafty Factor =20%3.3Total Moisture Load20 kg/hr. naitica dehumidifiers dehumidifir/buy